- indirect heating tank
- outdoor temperature sensor
- boiler circulation pump and/or indirect heating tank loading
- thermostat for high-precision indoor temperature regulation
- systems of remote control and comprehensive monitoring of heating system components using the Rs485 protocol
Parameter |
Clever L40 (KVA-0.04H) |
Clever L50 (KVA-0.05H) |
Clever L80 (KVA-0.08H) |
Clever L90 (KVA-0.09H) |
|
---|---|---|---|---|---|
Rated heat output in 80/60 heating mode,kW |
Rated heat output in 80/60 heating mode,kW
40 |
Rated heat output in 80/60 heating mode,kW
50 |
Rated heat output in 80/60 heating mode,kW
80 |
Rated heat output in 80/60 heating mode,kW
90 |
|
Minimum heat output in 80/60 heating mode |
Minimum heat output in 80/60 heating mode,kW
13 |
Minimum heat output in 80/60 heating mode,kW
17 |
Minimum heat output in 80/60 heating mode,kW
27 |
Minimum heat output in 80/60 heating mode,kW
30 |
|
Efficiency, up to,% |
Efficiency, up to,%
92 |
Efficiency, up to,%
92 |
Efficiency, up to,%
92 |
Efficiency, up to,%
92 |
|
Rated natural gas flow,m3/h |
Efficiency, up to,m3/h
4,6 |
Efficiency, up to,m3/h
5,8 |
Efficiency, up to,m3/h
9,2 |
Efficiency, up to,m3/h
9,8 |
|
Gas type,-//- |
Gas type,-//-
natural gas GOST 5542-2014 |
||||
Rated gas pressure,Pa |
Rated gas pressure,Pa
1700-2500 |
||||
Maximum operating heat transfer medium pressure at the boiler inlet, max. |
Maximum operating heat transfer medium pressure at the boiler inlet, max.,MPa
0,6 |
||||
Minimum operating heat transfer medium pressure |
Minimum operating heat transfer medium pressure,MPa
0,15 |
||||
Nominal flow rate of heat transfer medium (water) through the heat exchanger, (min.)* |
Nominal flow rate of heat transfer medium (water) through the heat exchanger, (min.)*,l/min
33 |
Nominal flow rate of heat transfer medium (water) through the heat exchanger, (min.)*,l/min
37 |
Nominal flow rate of heat transfer medium (water) through the heat exchanger, (min.)*,l/min
60 |
Nominal flow rate of heat transfer medium (water) through the heat exchanger, (min.)*,l/min
67 |
|
Flow resistance |
Flow resistance,MPa
0,020 |
Flow resistance,MPa
0,025 |
|||
Fuel-air ratio in exhaust gases |
Fuel-air ratio in exhaust gases,–
1,5-1,8 |
||||
Flue diameter |
Flue diameter,mm;
200 |
||||
Temperature of exhaust gases at minimum heat output, min. |
Temperature of exhaust gases at minimum heat output, min.,°С;
80 |
||||
Exhaust gas temperature at maximum heat output |
Exhaust gas temperature at maximum heat output,°С;
165 |
||||
Boiler rarefaction |
Boiler rarefaction,Pa;
5-12 |
||||
CO content in combustion products, max. |
CO content in combustion products, max.,mg/m3;
100 |
||||
NOx content in combustion products, max. |
NOx content in combustion products, max.,mg/m3;
200 |
||||
Mass flow of combustion products at rated heat output |
Mass flow of combustion products at rated heat output,kg/s
0,023 |
Mass flow of combustion products at rated heat output,kg/s
0,027 |
Mass flow of combustion products at rated heat output,kg/s
0,045 |
Mass flow of combustion products at rated heat output,kg/s
0,05 |
|
Mass flow of combustion products at minimum heat output |
Mass flow of combustion products at minimum heat output,kg/s
0,011 |
Mass flow of combustion products at minimum heat output,kg/s
0,014 |
Mass flow of combustion products at minimum heat output,kg/s
0,02 |
Mass flow of combustion products at minimum heat output,kg/s
0,022 |
|
Water volume in heat exchanger |
Water volume in heat exchanger,I
10 |
Water volume in heat exchanger,I
14 |
|||
Heat transfer area |
Heat transfer area,m2
5 |
Heat transfer area,m2
6 |
Heat transfer area,m2
9 |
Heat transfer area,m2
10 |
|
Combustion chamber volume |
Combustion chamber volume,m3
0,07 |
Combustion chamber volume,m3
0,12 |
|||
Maximum output water temperature taking into account control properties: |
Maximum output water temperature taking into account control properties:,°С
100 |
||||
Temperature controller operating range |
Temperature controller operating range,°С
50-95 |
||||
Connection dimensions along the water circuit |
Connection dimensions along the water circuit,–
G-2'' |
Connection dimensions along the water circuit,–
DN50 flange connection |
|||
Gas connection dimensions |
Gas connection dimensions,inch
G-3/4'' |
Gas connection dimensions,inch
G-11/4'' |
|||
Exhaust gas pipe connection dimensions |
Exhaust gas pipe connection dimensions,mm
198 |
||||
Power supply network parameters |
Power supply network parameters,V/Hz
230/50 |
||||
Power consumption (without optional equipment, when operating at nominal mode) |
Power consumption (without optional equipment, when operating at nominal mode),W
34 |
Power consumption (without optional equipment, when operating at nominal mode),W
42 |
|||
Service life |
Service life,years
10 |
||||
Dimensions: |
Dimensions:,mm
see Fig. 2,1/ 2,2 |
||||
Weight: - net weight |
Weight: - net weight,kg
77 |
Weight: - net weight,kg
80 |
Weight: - net weight,kg
135 |
Weight: - net weight,kg
140 |
|
- gross weight |
- gross weight,kg
87 |
- gross weight,kg
90 |
- gross weight,kg
155 |
- gross weight,kg
160 |